- Estimated Lead Time: 6-8 Weeks
- Manufacturer: Honeywell
- C6097A1046
- Pressure switch with manual reset, 10 in. wc min, 12 in. wc max setpoint
- Pressure Switches are safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure systems.
- For use with natural gas, liquid propane (LP) gas, or air.
- Diaphragm-actuated safety-limit switch.
- Switch can be wired to turn on alarm.
- C6097A models break control circuit at setpoint on pressure fall.
- C6097B models break control circuit at setpoint on pressure rise.
- Lockout with manual reset and recycle options.
- Lockout models have external manual reset button.
- Removable transparent cover protects scaleplate and adjusting knob.
- Pipe tappings allow selection of positive pressure (air only) or venting connections (NPT mount only).
- 1/4 in. NPT or flange mount models for direct mounting to Honeywell Integrated Valve Train.
- Optional switch position indicator lamp available.
- IP54 enclosure standard.
- Ranges: 0.4 to 5 in.wc, 3 to 21 in.wc, 12 to 60 in.wc or 1.5 to 7 psi.
- Surge orifice.
- Integral vent limiter on all models.
- Application : Safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure changes
- Dimensions (in.) : 2 19/32 in. high x 2 23/32 in. wide x 2 23/32 in. deep
- Dimensions (mm) : 66 mm high x 69 mm wide x 69 mm deep
- Mounting : Flange Mount
- Electrical Ratings : Ignition Transformer: 540 VA, Pilot Valve: 50 VA. Main Valve: 400 VA with 2-1/2 times inrush
- Approvals, Underwriters Laboratories Inc. : Component Listed, MP 2168-8-1
- Approvals, Canadian Standards Association : File # 95329 Certificate 2632-01
- Electrical Connections : Screw terminals
- Contact Ratings : 120 Vac Switch Contact-- 3.0 AFL, 18.0 ALR, 5.0 A resistive; 240 Vac Switch Contact-- 3.0 AFL, 18.0 ALR, 5.0 A resistive
- Operating Temperature Range (F) : -40 F to +140 F
- Operating Temperature Range (C) : -40 C to +60 C
- Approvals, Swiss RE : Acceptable
- Approvals, Factory MutualJI 2D4A1.AF
- Approvals, Others : CSD-1 AFB: Acceptable
- Operating Range (psi) : 12 to 60 in. wc
- Operating Range (kPa) : 3.0 to 15 kPa
- Differential Pressure Range (psi) : max. 10 in. wc @ min. setpoint; max. 12 in. wc @ max. setpoint
- Differential Pressure Range (kPa) : max. 2.5 kPa @ min. setpoint; max. 3.0 kPa @ max. setpoint:
- Differential Type : Additive
- Switch Operation : Manual Reset
- Switching Action : Break on pressure fall
- Shipping Weight : 1.3 Kg
Distributor of Industrial Automation Parts
One Stop Sourcing and Supply
Fast delivery, reliable combined shipping
20 years of experience
Leading industry innovation
Flexible Payment
Pay in 20+ local currencies
Ship worldwide via DHL, FedEx, UPS & more

September 26, 2025
Item Number:c6097a1046
Category: Honeywell
Price: $86.40 USD / €78.62 EUR
C6097A1046 -- Honeywell -- FLANGE MOUNT,12-60"W.C. W/MANUAL RESET
Details
Related Items
Invalid Date
DC2800 Universal Digital Controller packs new powerful features in the popular 1/4 DIN size.

Invalid Date
Honeywell Inc 129464 N Uv Power Tube 40 to 250 F for C 7035C

Invalid Date
honeywell Honeywell FC1000A1001 C7027A1049 program controller R4343E1014

Invalid Date
flame UV Amplifier, Dynamic Self-Check primary safety control relay modules