\n
- Estimated Lead Time : 1 Weeks \n
- Manufacturer : Phoenix Contact \n
- Orderkey : 2866789 \n
- Packing unit : 1 pc \n
- Catalog page : Page 210 (C-4-2017) \n
- GTIN : 4046356421720 \n
- Weight per Piece (excluding packing) : 3,815.800 g \n
- Custom tariff number : 85044030 \n
- Country of origin : TH (Thailand) \n
- Width : 180 mm \n
- Height : 130 mm \n
- Depth : 125 mm \n
- Width with alternative assembly : 122 mm \n
- Height with alternative assembly : 130 mm \n
- Depth with alternative assembly : 183 mm \n
- Degree of protection : IP20 \n
- Ambient temperature (operation) : -25 __ ... 70 __ (> 60 __ Derating: 2.5 %/K) \n
- Ambient temperature (start-up type tested) : -40 __ \n
- Ambient temperature (storage/transport) : -40 __ ... 85 __ \n
- Max. permissible relative humidity (operation) : <= 95 % (at 25 __, non-condensing) \n
- Climatic class : 3K3 (in acc. with EN 60721) \n
- Degree of pollution : 2 \n
- Installation height : 4000 m \n
- Nominal input voltage range : 100 V AC ... 240 V AC \n: 120 V DC ... 300 V DC (UL 508 <= 250 V DC) \n
- Input voltage range : 85 V AC ... 264 V AC \n90 V DC ... 300 V DC (UL 508: <= 250 V DC) \n
- Dielectric strength maximum : 300 V AC \n
- AC frequency range : 45 Hz ... 65 Hz \n
- Frequency range DC : 0 Hz \n
- Discharge current to PE : < 3.5 mA \n
- Current consumption : 8.8 A (120 V AC) \n4.6 A (230 V AC) \n9.5 A (110 V DC) \n4.7 A (220 V__C) \n
- Nominal power consumption : 1030 W \n
- Inrush surge current : < 15 A (typical) \n
- Mains buffering : > 35 ms (120 V AC) \n: > 35 ms (230 V AC) \n
- Input fuse : 20 A (slow-blow, internal) \n
- Choice of suitable circuit breakers : 16 A ... 20 A (AC: Characteristics B, C, D, K) \n
- Type of protection : Transient surge protection \n
- Protective circuit/component : Varistor, gas-filled surge arrester \n
- Nominal output voltage : 24 V DC 1% \n
- Setting range of the output voltage (USet) : 18 V DC ... 29.5 V DC (> 24 V__C, constant capacity restricted) \n
- Nominal output current (IN) : 40 A (-25___C_...60___C, UOUT=_24____C) \n
- POWER BOOST (IBoost) : 45 A (-25___...40_ permanent, UOUT_= 24____C ) \n
- Selective Fuse Breaking (ISFB) : 215 A (12 ms) \n
- Derating : 60 __ ... 70 __ (2.5%/K) \n
- Connection in parallel : Yes, for redundancy and increased capacity \n
- Connection in series : yes \n
- Feedback resistance : max. 35 V DC \n
- Circuit breaker against surge voltage at output by invasive foreign matter : < 35 V DC \n
- Residual ripple : < 30 mVPP_(with nominal values) \n
- Output power : 960 W \n
- Typical response time : < 0.7 s \n
- Maximum power dissipation in no-load condition : 14 W \n
- Power loss nominal load max. : 80 W \n
- Net weight : 3.3 kg \n
- Efficiency : > 92 % (for 230 V AC and nominal values) \n
- Insulation voltage input/output : 4 kV AC (type test) \n
- : 2 kV AC (routine test) \n
- Insulation voltage input / PE : 3.5 kV AC (type test) \n
- : 2 kV AC (routine test) \n
- Insulation voltage output / PE : 500 V DC (routine test) \n
- Protection class : I \n
- Degree of protection : IP20 \n
- MTBF (IEC 61709, SN 29500) : > 900000 h (25 __) \n: > 530000 h (40 __) \n
- Mounting position : horizontal DIN rail NS 35, EN 60715 \n
- Assembly instructions : alignable: PN_>=50%, 5__m horizontally, 15__m next to active components, 50__m vertically \nalignable: PN_<50%, 0__m horizontally, 40__m vertically top, 20 mm vertically bottom \n
- Connection method : Screw connection \n
- Conductor cross section solid min. : 0.2 mm_ \n
- Conductor cross section solid max. : 6 mm_ \n
- Conductor cross section flexible min. : 0.2 mm_ \n
- Conductor cross section flexible max. : 4 mm_ \n
- Conductor cross section AWG min. : 14 \n
- Conductor cross section AWG max. : 10 \n
- Stripping length : 7 mm \n
- Screw thread : M3 \n
- Connection method : Screw connection \n
- Conductor cross section solid min. : 0.5 mm_ \n
- Conductor cross section solid max. : 16 mm_ \n
- Conductor cross section flexible min. : 0.5 mm_ \n
- Conductor cross section flexible max. : 16 mm_ \n
- Conductor cross section AWG min. : 8 \n
- Conductor cross section AWG max. : 6 \n
- Stripping length : 10 mm \n
- Screw thread : M4 \n
- Conductor cross section solid min. : 0.2 mm_ \n
- Conductor cross section solid max. : 6 mm_ \n
- Conductor cross section flexible min. : 0.2 mm_ \n
- Conductor cross section flexible max. : 4 mm_ \n
- Conductor cross section AWG min. : 24 \n
- Conductor cross section AWG max. : 10 \n
- Screw thread : M3 \n
- Electromagnetic compatibility : Conformance with EMC Directive 2014/30/EU \n
- Noise emission : EN 55011 (EN 55022) \n
- Noise immunity : EN 61000-6-2:2005 \n
- Connection in acc. with standard : CSA \n
- Standards/regulations : EN 61000-4-2 \n
- Contact discharge : 4 kV (Test Level 2) \n
- Standards/regulations : EN 61000-4-3 \n
- Frequency range : 80 MHz ... 1 GHz \n
- Test field strength : 10 V/m (Test Level 3) \n
- Frequency range : 1.4 GHz ... 2 GHz \n
- Test field strength : 3 V/m (Test Level 2) \n
- Standards/regulations : EN 61000-4-4 \n
- Comments : Criterion B \n
- Standards/regulations : EN 61000-4-5 \n
- Signal : 1 kV (Test Level 2 - asymmetrical) \n
- Standards/regulations : EN_61000-6-3 -- EN_61000-4-6 \n
- Frequency range : 0.15 MHz ... 80 MHz \n
- Voltage : 10 V (Test Level 3) \n
- Low Voltage Directive : Conformance with LV directive 2006/95/EC \n
- Standard - Electrical safety : IEC 60950-1/VDE 0805 (SELV) \n
- Standard-Electronic equipment for use in electrical power installations and their assembly into electrical power installations : EN 50178/VDE 0160 (PELV) \n
- Standard-Safety extra-low voltage : IEC 60950-1 (SELV) and EN 60204-1 (PELV) \n
- Standard - Safe isolation : DIN VDE 0100-410 -- DIN VDE 0106-101 \n
- Standard-Protection against shock currents, basic requirements for protective separation in electrical equipment : EN 50178 \n
- Standard-Limitation of mains harmonic currents : EN 61000-3-2 \n
- Standard - Equipment safety : BG (design tested) \n
- Standard - Approval for medical use : IEC 60601-1, 2 x MOOP \n
- Shipbuilding approval : DNV__L_(EMC__), ABS, LR, RINA, NK, BV \n
- UL approvals : UL Listed UL 508 -- UL/C-UL Recognized UL 60950-1 -- UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) \n
- Shock : 18 ms, 30g, in each space direction (according to IEC 60068-2-27) \n
- Vibration (operation) : < 15 Hz, amplitude _2.5 mm (according to IEC 60068-2-6) \n: 15 Hz ... 150 Hz, 2.3g, 90 min. \n
- Information technology equipment - safety (CB__cheme) : CB Scheme \n
- Rail applications : EN 50121-4 \n
- Overvoltage category (EN 62477-1) : III \n
- China RoHS : Environmentally Friendly Use Period = 25; \n
- Shipping Weight : 5 Kg \n